編輯參考組態檔案(RCF)

若要啟動新授權的連接埠、您必須編輯最新版的RCF、然後取消註釋適用的連接埠詳細資料。預設授權會啟動連接埠0/1到0/16和0/55到0/56、而新授權的連接埠則會在連接埠0/17到0/54之間、視可用授權的類型和數量而定。

附註 如果您嘗試編輯先前安裝的RCF、程序可能會失敗、因為RCF中有其他區域的現有組態、請參閱 [Edit a previously installed RCF file]

如需有關用於B3作業 叢集交換器的可用授權類型詳細資料、請參閱 "安裝B封閉 環境叢集交換器的授權"

例如、若要啟動SW-BES54248-40-100g-LIC授權、您必須取消註解RCF中的下列章節:

.
.
!
! 2-port or 6-port 40/100GbE node port license block
!
interface 0/49
no shutdown
description "40/100GbE Node Port"
!speed 100G full-duplex
speed 40G full-duplex
service-policy in WRED_100G
spanning-tree edgeport
mtu 9216
switchport mode trunk
datacenter-bridging
priority-flow-control mode on
priority-flow-control priority 5 no-drop
exit
exit
!
interface 0/50
no shutdown
description "40/100GbE Node Port"
!speed 100G full-duplex
speed 40G full-duplex
service-policy in WRED_100G
spanning-tree edgeport
mtu 9216
switchport mode trunk
datacenter-bridging
priority-flow-control mode on
priority-flow-control priority 5 no-drop
exit
exit
!
interface 0/51
no shutdown
description "40/100GbE Node Port"
speed 100G full-duplex
!speed 40G full-duplex
service-policy in WRED_100G
spanning-tree edgeport
mtu 9216
switchport mode trunk
datacenter-bridging
priority-flow-control mode on
priority-flow-control priority 5 no-drop
exit
exit
!
interface 0/52
no shutdown
description "40/100GbE Node Port"
speed 100G full-duplex
!speed 40G full-duplex
service-policy in WRED_100G
spanning-tree edgeport
mtu 9216
switchport mode trunk
datacenter-bridging
priority-flow-control mode on
priority-flow-control priority 5 no-drop
exit
exit
!
interface 0/53
no shutdown
description "40/100GbE Node Port"
speed 100G full-duplex
!speed 40G full-duplex
service-policy in WRED_100G
spanning-tree edgeport
mtu 9216
switchport mode trunk
datacenter-bridging
priority-flow-control mode on
priority-flow-control priority 5 no-drop
exit
exit
!
interface 0/54
no shutdown
description "40/100GbE Node Port"
speed 100G full-duplex
!speed 40G full-duplex
service-policy in WRED_100G
spanning-tree edgeport
mtu 9216
switchport mode trunk
datacenter-bridging
priority-flow-control mode on
priority-flow-control priority 5 no-drop
exit
exit
!
.
.
附註 對於0/49到0/54(含)之間的高速連接埠、請針對每個連接埠取消註解、但在RCF中只取消註釋一條*速度*線路、以便針對每個連接埠:
  • 速度100公克全雙工

  • 速度40G全雙工

如範例所示。

對於0/17到0/48(含)之間的低速度連接埠、請在啟用適當授權後、取消註釋整個8埠區段。

編輯先前安裝的RCF檔案

編輯之前安裝的RCF檔案並執行「套用指令碼」之後、您可能會收到下列錯誤訊息:

(CS1)# script apply BES-53248_RCF_v1.6-Cluster-HA.scr
Are you sure you want to apply the configuration script? (y/n) y

選擇* y*後、您會收到下列錯誤訊息:

config
 ...
 match cos 5
 Unrecognized command : match cos 5
 Error! in configuration script file at line number 40.
 CLI Command :: match cos 5.
 Aborting script.

若要避免或解決此問題、您可以選擇下列其中一個選項: