Skip to main content
E-Series Systems

Replace DIMMs in EF300 or EF600

Contributors netapp-driley NetAppZacharyWambold netapp-jolieg netapp-jsnyder

You can replace a DIMM in an EF300 or EF600 array.

About this task

To replace a DIMM, you must verify the cache size of your controller, place the controller offline, remove the controller, remove the DIMMs, and install the new DIMMs in your controller. Then you can bring your controller back online and verify the storage array is working properly.

Before you begin
  • Review Requirements for replacing an EF300 or EF600 DIMM.

  • Make sure that no volumes are in use or that you have a multipath driver installed on all hosts using these volumes.

  • Make sure you have the following:

    • A replacement DIMM.

    • An ESD wristband, or you have taken other antistatic precautions.

    • A flat, static free work area.

    • Labels to identify each cable that is connected to the controller canister.

    • A management station with a browser that can access SANtricity System Manager for the controller. (To open the System Manager interface, point the browser to the controller's domain name or IP address.)

Step 1: Determine if you need to replace a DIMM

Verify the cache size of your controller before replacing the DIMMS.

Steps
  1. Access the Storage Array profile for the controller. From SANtricity System Manager, go to Support  Support Center. From the Support Resources page, select Storage Array Profile.

  2. Scroll down or use the Search field to locate the Data Cache Module information.

  3. If one of the following is present, note the DIMM's location and continue with remaining procedures in this section to replace the DIMMs on your controller:

    • A failed DIMM, or a DIMM reporting Data Cache Module as not optimal.

    • A DIMM with a mismatched Data Cache Module capacity.

Step 2: Place controller offline

Place the controller offline so you can safely remove and replace the DIMMs.

Steps
  1. From SANtricity System Manager, review the details in the Recovery Guru to confirm that there is an issue with a mismatched memory and to ensure no other items must be addressed first.

  2. From the Details area of the Recovery Guru, determine which DIMM to replace.

  3. Back up the storage array's configuration database using SANtricity System Manager.

    If a problem occurs when you remove a controller, you can use the saved file to restore your configuration. The system will save the current state of the RAID configuration database, which includes all data for volume groups and disk pools on the controller.

    • From System Manager:

      1. Select Support  Support Center  Diagnostics.

      2. Select Collect Configuration Data.

      3. Click Collect.

        The file is saved in the Downloads folder for your browser with the name, configurationData-<arrayName>-<dateTime>.7z.

  4. If the controller is not already offline, take it offline now using SANtricity System Manager.

    1. Select Hardware.

    2. If the graphic shows the drives, select Show back of shelf to show the controllers.

    3. Select the controller that you want to place offline.

    4. From the context menu, select Place offline, and confirm that you want to perform the operation.

      Note If you are accessing SANtricity System Manager using the controller you are attempting to take offline, a SANtricity System Manager Unavailable message is displayed. Select Connect to an alternate network connection to automatically access SANtricity System Manager using the other controller.
  5. Wait for SANtricity System Manager to update the controller's status to offline.

    Note Do not begin any other operations until after the status has been updated.
  6. Select Recheck from the Recovery Guru, and confirm that the OK to remove field in the Details area displays Yes, indicating that it is safe to remove this component.

Step 3: Remove controller canister

You remove the failed controller canister so you can replace your DIMMs with new ones.

Steps
  1. Put on an ESD wristband or take other antistatic precautions.

  2. Label each cable that is attached to the controller canister.

  3. Disconnect all the cables from the controller canister.

    Caution To prevent degraded performance, do not twist, fold, pinch, or step on the cables.
  4. Confirm that the Cache Active LED on the back of the controller is off.

  5. Squeeze the handles on either side of the controller, and pull back until it releases from the shelf.

    Squeeze handles to remove controller
  6. Using two hands and the handles, slide the controller canister out of the shelf. When the front of the controller is free of the enclosure, use two hands to pull it out completely.

    Caution Always use two hands to support the weight of a controller canister.
    Use two hands to support weight of controller as you remove
  7. Place the controller canister on a flat, static-free surface.

Step 4: Remove DIMMs

If there is a memory mismatch present, replace the DIMMs in your controller.

Steps
  1. Remove the controller canister's cover by unscrewing the single thumbscrew and lifting the lid open.

  2. Confirm that the green LED inside the controller is off.

    If this green LED is on, the controller is still using battery power. You must wait for this LED to go off before removing any components.

  3. Locate the DIMMs on your controller.

  4. Note the orientation of the DIMM in the socket so that you can insert the replacement DIMM in the proper orientation.

    Note A notch at the bottom of the DIMM helps you align the DIMM during installation.
  5. Slowly push apart on the two DIMM ejector tabs on either side of the DIMM to eject the DIMM from its slot, and then slide it out of the slot.

    Press the ejector tab downs on the DIMM slot
    Remove the DIMM
    Caution Carefully hold the DIMM by the edges to avoid pressure on the components on the DIMM circuit board.

    The number and placement of system DIMMs depends on the model of your system.

Step 5: Install new DIMMs

Install a new DIMM to replace the old one.

Steps
  1. Hold the DIMM by the corners, and align it to the slot.

    The notch among the pins on the DIMM should line up with the tab in the socket.

  2. Insert the DIMM squarely into the slot.

    The DIMM fits tightly in the slot, but should go in easily. If not, realign the DIMM with the slot and reinsert it.

    Note Visually inspect the DIMM to verify that it is evenly aligned and fully inserted into the slot.
  3. Push carefully, but firmly, on the top edge of the DIMM until the latches snap into place over the notches at the ends of the DIMM.

    Note DIMMs fit tightly. You might need to gently press on one side at a time and secure with each tab individually.
    Insert DIMMS into the slot and secure with tabs

Step 6: Reinstall controller canister

After installing the new DIMMs, reinstall the controller canister into the controller shelf.

Steps
  1. Lower the cover on the controller canister and secure the thumbscrew.

  2. While squeezing the controller handles, gently slide the controller canister all the way into the controller shelf.

    Note The controller audibly clicks when correctly installed into the shelf.
    Install DIMM into slot on the controller
  3. Reconnect all the cables.

Step 7: Complete DIMMs replacement

Place the controller online, collect support data, and resume operations.

Steps
  1. Place controller online.

    1. In System Manager, navigate to the Hardware page.

    2. Select Show back of controller.

    3. Select the controller with the replaced DIMMs.

    4. Select Place online from the drop-down list.

  2. As the controller boots, check the controller LEDs.

    When communication with the other controller is reestablished:

    • The amber Attention LED remains on.

    • The Host Link LEDs might be on, blinking, or off, depending on the host interface.

  3. When the controller is back online, confirm that its status is Optimal and check the controller shelf's Attention LEDs.

    If the status is not Optimal or if any of the Attention LEDs are on, confirm that all cables are correctly seated and the controller canister is installed correctly. If necessary, remove and reinstall the controller canister.

    Note If you cannot resolve the problem, contact technical support.
  4. Click Hardware  Support  Upgrade Center to ensure that the latest version of SANtricity OS is installed.

    As needed, install the latest version.

  5. Verify that all volumes have been returned to the preferred owner.

    1. Select Storage  Volumes. From the All Volumes page, verify that volumes are distributed to their preferred owners. Select More  Change ownership to view volume owners.

    2. If volumes are all owned by preferred owner continue to Step 6.

    3. If none of the volumes are returned, you must manually return the volumes. Go to More  Redistribute volumes.

    4. If there is no Recovery Guru present or if following the Recovery Guru steps the volumes are still not returned to their preferred owners contact support.

  6. Collect support data for your storage array using SANtricity System Manager.

    1. Select Support  Support Center  Diagnostics.

    2. Select Collect Support Data.

    3. Click Collect.

      The file is saved in the Downloads folder for your browser with the name, support-data.7z.

What's next?

Your DIMM replacement is complete. You can resume normal operations.