Power on SG6000-CN controller and verify operation
Power on the controller after completing maintenance.
-
You have installed the controller in a cabinet or rack and connected the data and power cables.
-
You have physically located the controller in the data center.
-
Power on the SG6000-CN controller and monitor the controller LEDs and boot-up codes using one of the following methods:
-
Press the power switch on the front of the controller.
-
Use the controller BMC interface:
-
Access the controller BMC interface.
-
Select Power Control.
-
Select Power On Server and then select Perform Action.
Use the BMC interface to monitor start-up status.
-
-
-
Confirm that the appliance controller displays in the Grid Manager and with no alerts.
It might take up to 20 minutes for the controller to display in the Grid Manager.
-
Confirm that the new SG6000-CN controller is fully operational:
-
Log in to the grid node using PuTTY or another ssh client:
-
Enter the following command:
ssh admin@grid_node_IP
-
Enter the password listed in the
Passwords.txt
file. -
Enter the following command to switch to root:
su -
-
Enter the password listed in the
Passwords.txt
file.When you are logged in as root, the prompt changes from
$
to#
.
-
-
Enter the following command and verify that it returns the expected output:
cat /sys/class/fc_host/*/port_state
Expected output:
Online Online Online Online
If the expected output is not returned, contact technical support.
-
Enter the following command and verify that it returns the expected output:
cat /sys/class/fc_host/*/speed
Expected output:
16 Gbit 16 Gbit 16 Gbit 16 Gbit
If the expected output is not returned, contact technical support.
-
From the Nodes page in Grid Manager, make sure that the appliance node is connected to the grid and does not have any alerts.
Don't take another appliance node offline unless this appliance has a green icon.
-
-
Optional: Install the front bezel, if one was removed.