Swap out a power supply - ASA A900

Contributors netapp-jsnyder

Swapping out a power supply involves turning off, disconnecting, and removing the power supply and installing, connecting, and turning on the replacement power supply.

All other components in the system must be functioning properly; if not, you must contact technical support.

About this task
  • The power supplies are redundant and hot-swappable.

  • This procedure is written for replacing one power supply at a time.

    Note It is a best practice to replace the power supply within two minutes of removing it from the chassis. The system continues to function, but ONTAP sends messages to the console about the degraded power supply until the power supply is replaced.
  • There are four power supplies in the system.

  • Power supplies are auto-ranging.

    Important Do not mix PSUs with different efficiency ratings. Always replace like for like.
Steps
  1. Identify the power supply you want to replace, based on console error messages or through the LEDs on the power supplies.

  2. If you are not already grounded, properly ground yourself.

  3. Turn off the power supply and disconnect the power cables:

    1. Turn off the power switch on the power supply.

    2. Open the power cable retainer, and then unplug the power cable from the power supply.

  4. Press and hold the terra cotta button on the power supply handle, and then pull the power supply out of the chassis.

    CAUTION:

    When removing a power supply, always use two hands to support its weight.

    Animation - Remove/install PSU
    drw 9000 remove install psu module

    Callout number 1

    Locking button

  5. Make sure that the on/off switch of the new power supply is in the Off position.

  6. Using both hands, support and align the edges of the power supply with the opening in the system chassis, and then gently push the power supply into the chassis until it locks into place.

    The power supplies are keyed and can only be installed one way.

    Important Do not use excessive force when sliding the power supply into the system. You can damage the connector.
  7. Reconnect the power supply cabling:

    1. Reconnect the power cable to the power supply.

    2. Secure the power cable to the power supply using the power cable retainer.

      Once power is restored to the power supply, the status LED should be green.

  8. Turn on the power to the new power supply, and then verify the operation of the power supply activity LEDs.

    The green power LED lights when the PSU is fully inserted into the chassis and the amber attention LED flashes initially, but turns off after a few moments.

  9. Return the failed part to NetApp, as described in the RMA instructions shipped with the kit. See the Part Return & Replacements page for further information.